Ürünler

Sensör Pepperl+Fuchs
Endüktif Sensör Pepperl Fuchs NJ2,5-14GM-N-V1-Y21146
27 Ocak 2019
Sensör Pepperl Fuchs
Endüktif Sensör Pepperl Fuchs NJ2-11-N-G
27 Ocak 2019
Tümünü Göster

Endüktif Sensör Pepperl Fuchs NJ2-11-N


Sensör
Yakınlık Sensörü
Proximity Sensor
Endüktif Proximity Sensör
Inductive Proximity Sensor
Pepperl Fuchs
Pepperl Fuchs Sensör
Pepperl Fuchs Proximity Sensor
Pepperl Fuchs Yakınlık Sensörü
Pepperl Fuchs Endüktif Proximity Sensör
Pepperl Fuchs Inductive Proximity Sensor
Pepperl Fuchs NJ2-11-N
Pepperl NJ2-11-N
NJ2-11-N

Açıklama

Pepperl Fuchs NJ2-11-N Endüktif Sensör
Pepperl NJ2-11-N Inductive Sensor
Yaklaşım Sensörü Pepperl Fuchs NJ2-11-N
Pepperl Fuchs NJ2-11-N Yakınlık Sensörü
Inductive Sensor NJ2-11-N Pepperl-Fuchs
Endüktif Sensör NJ2-11-N Pepperl-Fuchs

Teknik veriler NJ2-11-N

General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance 2 mm
Installation flush
Assured operating distance 0 … 1.62 mm
Actual operating distance 1.8 … 2.2 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type 2-wire
Nominal ratings
Nominal voltage 8.2 V (Ri approx. 1 kΩ)
Switching frequency 0 … 3000 Hz
Hysteresis 0.5 … 3.5 typ. 2 %
Current consumption
Measuring plate not detected min. 3 mA
Measuring plate detected ≤ 1 mA
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
MTTFd 5887 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Compliance with standards and directives
Standard conformity
NAMUR EN 60947-5-6:2000
IEC 60947-5-6:1999
Approvals and certificates
FM approval
Control drawing 116-0165
UL approval cULus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature -25 … 100 °C (-13 … 212 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.34 mm2
Housing material PVDF
Sensing face PVDF
Degree of protection IP68
Cable
Bending radius > 10 x cable diameter
Data for application in connection with hazardous areas
Equipment protection level Ga , Gb , Gc (ic) , Da , Mb
General information
Use in the hazardous area see instruction manuals