Sensör
Yakınlık Sensörü
Proximity Sensor
Endüktif Proximity Sensör
Inductive Proximity Sensor
Pepperl Fuchs
Pepperl Fuchs Sensör
Pepperl Fuchs Proximity Sensor
Pepperl Fuchs Yakınlık Sensörü
Pepperl Fuchs Endüktif Proximity Sensör
Pepperl Fuchs Inductive Proximity Sensor
Pepperl Fuchs NBB15-U1K-E2-3G-3D
Pepperl NBB15-U1K-E2-3G-3D
NBB15-U1K-E2-3G-3D
Pepperl Fuchs NBB15-U1K-E2-3G-3D Endüktif Sensör
Pepperl NBB15-U1K-E2-3G-3D Inductive Sensor
Yaklaşım Sensörü Pepperl Fuchs NBB15-U1K-E2-3G-3D
Pepperl Fuchs NBB15-U1K-E2-3G-3D Yakınlık Sensörü
Inductive Sensor NBB15-U1K-E2-3G-3D Pepperl-Fuchs
Endüktif Sensör NBB15-U1K-E2-3G-3D Pepperl-Fuchs
General specifications | ||
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 15 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 … 12.15 mm | |
Actual operating distance | 13.5 … 16.5 mm typ. 15 mm | |
Reduction factor rAl | 0.33 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.74 | |
Reduction factor rBrass | 0.41 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 … 30 V | |
Switching frequency | 0 … 200 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | ≤ 2 V | |
Voltage drop at IL | ||
Voltage drop IL = 1 mA, switching element on | 0.5 … 2.3 V typ. 0.9 V | |
Voltage drop IL = 10 mA, switching element on | 0.8 … 2.2 V typ. 1.4 V | |
Voltage drop IL = 20 mA, switching element on | 0.9 … 2.3 V typ. 1.5 V | |
Voltage drop IL = 50 mA, switching element on | 0.9 … 2.5 V typ. 1.6 V | |
Voltage drop IL = 100 mA, switching element on | 1 … 2.6 V typ. 1.8 V | |
Voltage drop IL = 200 mA, switching element on | 1.2 … 2.8 V typ. 2 V | |
Operating current | 0 … 200 mA | |
Off-state current | 0 … 0.5 mA typ. 0.01 mA | |
Off-state current TU =40 °C, switching element off | ≤ 100 µA | |
No-load supply current | ≤ 20 mA | |
Time delay before availability | 80 ms | |
Operating voltage indicator | LED, green | |
Switching state indicator | LED, yellow | |
Functional safety related parameters | ||
MTTFd | 1242 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
FM approval | hazardous (classified) location Non-incendive |
|
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 … 85 °C (-13 … 185 °F) | |
Mechanical specifications | ||
Connection type | Connector plug M12 x 1 , 4-pin | |
Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
|
Core cross-section | up to 2.5 mm2 | |
Minimum core cross-section | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 | |
Maximum core cross-section | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Degree of protection | IP68 / IP69K | |
Mass | 225 g | |
Note | Tightening torque: 1.8 Nm (housing) | |
Equipment protection level Gc (nA) | ||
Certificate | PF 15CERT3754 X | |
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3G Ex nA IIC T6 Gc The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-15:2010 Ignition protection category “n” Use is restricted to the following stated conditions |
|
Special conditions | ||
Maximum operating current IL | The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted. | |
Maximum operating voltage UBmax | The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible. | |
Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list. |
|
at UBmax=30 V, IL=200 mA | 50 °C (122 °F) | |
at UBmax=30 V, IL=100 mA | 53 °C (127.4 °F) | |
at UBmax=30 V, IL=50 mA | 54 °C (129.2 °F) | |
Equipment protection level Dc (tc) | ||
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure “tc” Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
|
General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. | |
Special conditions | ||
Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list. |
|
at UBmax=30 V, IL=200 mA | 50 °C (122 °F) | |
at UBmax=30 V, IL=100 mA | 53 °C (127.4 °F) | |
at UBmax=30 V, IL=50 mA | 54 °C (129.2 °F) |