Ürünler

Pepperl Ultrasonik Sensörler
Endüktif Sensör Pepperl Fuchs FJ7-A2-Y20193
10 Aralık 2018
Ultrasonic Sensor Pepperl Fuchs
Endüktif Sensör Pepperl Fuchs FT3 K 2045/33 K
10 Aralık 2018
Tümünü Göster

Endüktif Sensör Pepperl Fuchs FJ7-N


Sensör
Yakınlık Sensörü
Proximity Sensor
Endüktif Proximity Sensör
Inductive Proximity Sensor
Pepperl Fuchs
Pepperl Fuchs Sensör
Pepperl Fuchs Proximity Sensor
Pepperl Fuchs Yakınlık Sensörü
Pepperl Fuchs Endüktif Proximity Sensör
Pepperl Fuchs Inductive Proximity Sensor
Pepperl Fuchs FJ7-N
Pepperl FJ7-N
FJ7-N

Açıklama

Pepperl Fuchs FJ7-N Endüktif Sensör
Pepperl FJ7-N Inductive Sensor
Yaklaşım Sensörü Pepperl Fuchs FJ7-N
Pepperl Fuchs FJ7-N Yakınlık Sensörü
Inductive Sensor FJ7-N Pepperl-Fuchs
Endüktif Sensör FJ7-N Pepperl-Fuchs

Teknik veriler FJ7-N

General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance 7 mm
Installation flush
Assured operating distance 0 … 5.67 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type 2-wire
Nominal ratings
Nominal voltage 8.2 V (Ri approx. 1 kΩ)
Operating voltage 5 … 25 V
Switching frequency 0 … 200 Hz
Hysteresis typ. %
Current consumption
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA
Switching state indicator LED, yellow
Functional safety related parameters
MTTFd 4080 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Compliance with standards and directives
Standard conformity
NAMUR EN 60947-5-6:2000
Standards EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing 116-0165
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature -25 … 100 °C (-13 … 212 °F)
Mechanical specifications
Connection type cable PUR , 2 m
Core cross-section 0.34 mm2
Housing material brass, zinc plated
Sensing face POM
Degree of protection IP67
Cable
Bending radius > 10 x cable diameter
Data for application in connection with hazardous areas
Equipment protection level Gb , Gc (ic) , Mb
Equipment protection level Gb
Type of protection intrinsic safety
CE marking [*PD-Z02585A*]
Certificates
Appropriate type FJ7-N…
ATEX certificate PTB 00 ATEX 2032 X
ATEX marking II 2G Ex ia IIC T6…T1 Gb
Standards EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificate IECEx PTB 11.0021X
IECEx marking Ex ia IIC T6…T1 Gb
Standards IEC 60079-0:2011 , IEC 60079-11:2011
Effective internal inductivity max. 65 nF
A cable length of 10 m is considered.
Effective internal inductance max. 220 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperature Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 62 °C (143.6 °F)
T5 : 77 °C (170.6 °F)
T4 : 81 °C (177.8 °F)
T3 : 81 °C (177.8 °F)
T2 : 81 °C (177.8 °F)
T1 : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 54 °C (129.2 °F)
T5 : 63 °C (145.4 °F)
T4 : 63 °C (145.4 °F)
T3 : 63 °C (145.4 °F)
T2 : 63 °C (145.4 °F)
T1 : 63 °C (145.4 °F)
Equipment protection level Gc (ic)
Type of protection intrinsic safety
CE marking [*PD-Z02586A*]
Certificates
ATEX certificate PF 13 CERT 2895 X
ATEX marking II 3G Ex ic IIC T6…T1 Gc
Standards EN 60079-0:2012+A11:2013 , EN 60079-11:2012
Effective internal inductivity max. 65 nF
A cable length of 10 m is considered.
Effective internal inductance max. 220 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperature Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 62 °C (143.6 °F)
T5 : 77 °C (170.6 °F)
T4 : 81 °C (177.8 °F)
T3 : 81 °C (177.8 °F)
T2 : 81 °C (177.8 °F)
T1 : 81 °C (177.8 °F)
at Ui = 20 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 54 °C (129.2 °F)
T5 : 63 °C (145.4 °F)
T4 : 63 °C (145.4 °F)
T3 : 63 °C (145.4 °F)
T2 : 63 °C (145.4 °F)
T1 : 63 °C (145.4 °F)
Equipment protection level Mb
Type of protection intrinsic safety
Certificates
Appropriate type FJ7-N…
IECEx certificate IECEx PTB 11.0021X
IECEx marking Ex ia I Mb
Standards IEC 60079-0:2011 , IEC 60079-11:2011
Effective internal inductivity max. 65 nF
A cable length of 10 m is considered.
Effective internal inductance max. 220 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperature Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F)
General information
Use in the hazardous area see instruction manuals