Ürünler

I-O Haberleşme Modülü Murr 55923
I/O Haberleşme Modülü Murr 55923
5 Nisan 2017
Sensör Kutusu Phoenix Contact 1516218 SACB-10-3-L-M16-M8
Sensör Kutusu Phoenix Contact 1516218 SACB-10/3-L-M16-M8
5 Nisan 2017
Tümünü Göster

I/O Haberleşme Modülü Murr 55920-Murr 55922


Modül
Input-Output
Digital I/O Modül
Output
Haberleşme Modülü
Murr
Murr Digital Input-Output
Murr Digital I/O Modül
Murr Output
Murr Haberleşme Modülü
Murr 55920
Murr 55922

Açıklama

I/O Haberleşme Modülü Murr 55920-Murr 55922

Murr 55920
DIGITAL IN-/OUTPUT MODULE
16 digital inputs and 16 digital outputs
Expansion module
Digital inputs
Digital outputs
DI16/DO16

Input

Sensor supply US 24 V DC (EN 61131-2), max. 700 mA per module
Type PNP (EN 61131-2)
Input filter 1 ms
Galvanic isolation 500 V DC between inputs and internal communication

Internal communication

Module Supply via system connection
Current consumption max. 25 mA

Connections

Fieldbus Ribbon cable connection
Sensor-system/actuator supply 8 × Spring clamp plug-in terminals, max. 2.5 mm² (max. 12 A)
I/O ports 32 × Spring clamp plug-in terminals, max. 2.5 mm²

General data

Protection IP20
Mounting method DIN-rail mountable (EN 60715)
Temperature range 0…+55 °C (storage temperature -20…+85 °C)
Dimensions H × W × D 117×56×47 mm

Output

Actuator supply UA 24 V DC (EN 61131-2), max. 12 A
Galvanic isolation 500 V DC between outputs and internal communication
Switching current per output max. 0.5 A (short-circuit and overload protected)
Lamp load 10 W

Murr 55922
DIGITAL OUTPUT MODULE
16 digital outputs
Expansion module
DO16

Internal communication

Module Supply via system connection
Current consumption max. 25 mA

Connections

Fieldbus Ribbon cable connection
Sensor-system/actuator supply 8 × Spring clamp plug-in terminals, max. 2.5 mm² (max. 12 A)
I/O ports 16 × Spring clamp plug-in terminals, max. 2.5 mm²

General data

Protection IP20
Mounting method DIN-rail mountable (EN 60715)
Temperature range 0…+55 °C (storage temperature -20…+85 °C)
Dimensions H × W × D 117×56×47 mm

Output

Actuator supply UA 24 V DC (EN 61131-2), max. 12 A
Switching current per output max. 2 A
Galvanic isolation 500 V DC between outputs and internal communication
Lamp load 40 W