Sensör
Yakınlık Sensörü
Proximity Sensor
Endüktif Proximity Sensör
Inductive Proximity Sensor
Pepperl Fuchs
Pepperl Fuchs Sensör
Pepperl Fuchs Proximity Sensor
Pepperl Fuchs Yakınlık Sensörü
Pepperl Fuchs Endüktif Proximity Sensör
Pepperl Fuchs Inductive Proximity Sensor
Pepperl Fuchs NBB15-U4K-N0
Pepperl NBB15-U4K-N0
NBB15-U4K-N0
Pepperl Fuchs NBB15-U4K-N0 Endüktif Sensör
Pepperl NBB15-U4K-N0 Inductive Sensor
Yaklaşım Sensörü Pepperl Fuchs NBB15-U4K-N0
Pepperl Fuchs NBB15-U4K-N0 Yakınlık Sensörü
Inductive Sensor NBB15-U4K-N0 Pepperl-Fuchs
Endüktif Sensör NBB15-U4K-N0 Pepperl-Fuchs
General specifications | ||
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 15 mm | |
Installation | flush | |
Assured operating distance | 0 … 12.15 mm | |
Actual operating distance | 13.5 … 16.5 mm typ. 15 mm | |
Reduction factor rAl | 0.33 | |
Reduction factor rCu | 0.31 | |
Reduction factor r304 | 0.74 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 … 300 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | yes | |
Short-circuit protection | yes | |
Current consumption | ||
Measuring plate not detected | min. 2.2 mA | |
Measuring plate detected | ≤ 1 mA | |
Switching state indicator | LED, yellow | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
|
Electromagnetic compatibility | NE 21:2007 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
Ambient conditions | ||
Ambient temperature | -25 … 100 °C (-13 … 212 °F) | |
Storage temperature | -40 … 100 °C (-40 … 212 °F) | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | ≤ 2.5 mm2 | |
Housing material | PA/metal | |
Sensing face | PA | |
Degree of protection | IP68 / IP69K | |
Mass | 225 g | |
Note | Tightening torque: 1.8 Nm (housing) | |
Equipment protection level Ga | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection “Intrinsic safety” Use is restricted to the following stated conditions |
|
Appropriate type | NBB15-U.K-N0… | |
Effective internal capacitance | max. 110 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 200 µH ; a cable length of 10 m is considered. | |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. | |
Equipment protection level Gb | ||
CE marking | [*PD-Z02585A*] | |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection “Intrinsic safety” Use is restricted to the following stated conditions |
|
Appropriate type | NBB15-U.K-N0… | |
Effective internal capacitance | max. 110 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 200 µH ; a cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. | |
Equipment protection level Gc (ic) | ||
Certificate | PF 13 CERT 2895 X | |
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3G Ex ic IIC T6…T1 Gc The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012, EN 60079-11:2012 Ignition protection category “ic” Use is restricted to the following stated conditions |
|
Effective internal capacitance | max. 110 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 200 µH ; A cable length of 10 m is considered. | |
Special conditions | ||
for Pi=34 mW, Ii=25 mA, T6 | 73 °C (163.4 °F) | |
for Pi=34 mW, Ii=25 mA, T5 | 88 °C (190.4 °F) | |
for Pi=34 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) | |
for Pi=64 mW, Ii=25 mA, T6 | 66 °C (150.8 °F) | |
for Pi=64 mW, Ii=25 mA, T5 | 81 °C (177.8 °F) | |
for Pi=64 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) | |
for Pi=169 mW, Ii=52 mA, T6 | 45 °C (113 °F) | |
for Pi=169 mW, Ii=52 mA, T5 | 60 °C (140 °F) | |
for Pi=169 mW, Ii=52 mA, T4-T1 | 89 °C (192.2 °F) | |
for Pi=242 mW, Ii=76 mA, T6 | 30 °C (86 °F) | |
for Pi=242 mW, Ii=76 mA, T5 | 45 °C (113 °F) | |
for Pi=242 mW, Ii=76 mA, T4-T1 | 74 °C (165.2 °F) | |
Equipment protection level Da | ||
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
|
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection “Intrinsic safety” Use is restricted to the following stated conditions |
|
Appropriate type | NBB15-U.K-N0… | |
Effective internal capacitance | max. 110 nF ; a cable length of 10 m is considered. | |
Effective internal inductance | max. 200 µH ; a cable length of 10 m is considered. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G; 2G; 3G |