General
Interbus Slave IP67 with
8 digital outputs
EMC
EN 61131-2 Product standard
EN 61000-4-2 ESD ………………………………………………………….. Contact ± 4 kV, air ± 8 kV
EN 61000-4-3 RF- Field & GSM ………………………………………. 10 V/m
EN 61000-4-4 Burst …………………………………………………………. ± 2 kV
EN 61000-4-5 Surge ………………………………………………………… asym./symm. ± 500 V (DC net input)
asym. ± 1 kV (Signal connections)
EN 61000-4-6 HF-asymmetric ………………………………………….. 10 V
EN 61000-4-8 Magnetic field 50 Hz ………………………………….. 30 A/m
EN 55011 Emission ………………………………………………………….. QP 40 dBμV/m (30 – 230 MHz)
………………………………………………………………………………………. QP 47 dBμV/m (230 – 1000 MHz) (class A)
Ambient conditions
Operating temperature ……………………………………………………… 0°C … +55°C
Storage temperature …………………………………………………………. -25°C … +70°C
Enclosure type according to EN60529 ……………………………….. IP 67
Mechanical ambient conditions
Oscillation according to EN 60068 Part 2-6 ………………………… 10 – 58 Hz; const. amplitude 0,35 mm
………………………………………………………………………………………. 58 – 150 Hz; const. acceleration 20 g
Shock according to EN 60068 Part 2-27 ……………………………… Amplitude 50 g, 11 ms duration
Connection possibilities
Supply cable …………………………………………………………………… 2 x connector 7/8″ (male and female connector)
Data cable ………………………………………………………………………. 2 x M12 connector 5-pin
(male and female connector reverse-key coding)
Inputs and diagnosis inputs………………………………………………… 8 x 5-pin M12 female connectors
Miscellaneous
Dimensions (LxWxH) ………………………………………………………. 225 x 63 x 39 mm
Mounting dimension…………………………………………………………. 208,5 ±0,5 mm
Weight …………………………………………………………………………… 760 g
Bus data
Transfer protocol …………………………………………………………….. Interbus-S acc. to DIN 19245
Transfer rates ………………………………………………………………….. 500 kBaud
Galvanic isolation ……………………………………………………………. 500 V between bus and internal logic
Ident. number ………………………………………………………………….. 03 hex
Power supply
Operation voltage UB ……………………………………………………….. 24 V DC
Operation voltage range ……………………………………………………. 18 … 30 V DC
Current consumption (without inputs)…………………………………. <= 120 mA
Sensor supply ………………………………………………………………….. max. 200 mA per socket
Short circuit protection for sensors …………………………………….. Multi-fuse,
up to 100 mA load: automatic start-up
from 100 mA load: a reset is required
Multi-fuse reaction time (time to trip) ………………………………… 1s at IK >= 1 A and 23 °C
Connector ……………………………………………………………………… 7/8” (Max.1,5 mm2)
Reverse polarity protection, inputs …………………………………….. yes
Outputs
Actuator current load ……………………………………………………….. max. 2 A per actuator
Cable length…………………………………………………………………….. With 0,75 mm² max. 10 m
With 0,34 mm² max. 5 m
Connector ……………………………………………………………………… M12 (Max.0,75 mm2)
Cycle frequency……………………………………………………………….. max. 50 Hz
Lamp load……………………………………………………………………….. max. 10 W